APM8xx Series AC Multi-function Smart Meter
Characteristic
Full Electric Parameters Measurement
● 3-phase (I, U, kW, kVar, kWh, Hz, cosφ)
● Current&Voltage Unbalance
● Harmonic (THD & 2~63rd)
● Real-time&Max Demand
● Extremum of this month&last month
● Zero-sequence Current
● 4-quadrant Energy
Diverse Extra Function Module
● Modular Design (Easy for Function Expansion)
● Support up to 3 Expanded Module at same time
DO/DI Switch Function Module ---MD82
● 2 DO Relay Output
● 8 DI Digital Input
● Save up to 128 pcs DO/DI Data in Main Body
● Paired with MLOG to save more DO/DI Records
SD Card Data Storage Module ---MLOG
● Expand Number of SOE Storage
● Support Storage of SD Cards up to 32GB (standard 4GB)
Extra RS485 Communication Module ---MCM
● Interface: RS485 Interface
● Protocol: MODBUS-RTU
● Support Salve&Master Mode
Ethernet Communication Module ---MCME
● Interface: RJ45 Interface
● Protocol: MODBUS-TCP/HTTP/DHCP/SMTP
● Could Serve as Serial Server
● Plus 1 Extra RS485 Interface
PROFIBUS-DP Communication Module ---MCMP
● Interface: PROFIBUS-DP Interface
● Protocol: PROFIBUS-DP
● Plus 1 Extra RS485 Interface
SOE Function (Main Body)
● Alarm Record (128 pcs records of 66 kinds&13 categories)
● DO/DI Record (128 pcs DO/DI records)
● Transient Record (800 pcs transient waveform records)
● Max Records pcs above could be expanded by SD Card
Multi-rate/Multi-tariff
● 4 Time zone
● 4 Tariff rate (Spike, Peak, Flat, Valley)
● 2 Time period list
● 14 Time period by day
Local Configuration
● Keypads HMI for Programming
● Setting through Adjustment Software
● Setting through WEB
● Setting through MODBUS communication
3-phase 4-wire connection
via 3 extra CTs
3-phase 3-wire connection
via 2 extra CTs & 2 extra PTs
The meter is equiped with standard 4G SD card while saving the data of electrical parameter, energy, event, SOE, alarm. Also, the setting of storage interval could be changed. (1 min interval for electrical parameter and 1 hour interval for energy)
Our users can select 3 of the optional modules at will even repeatly except for communication module. Also, the order of module installation could be random.
Except for wave record and SD card storage function, 0.2S measuring accuracy can also be a option. Besides, APM8xx can serve as reverse display meter (which means 3-phase electrical parameters measuring plus 8-channel reverse display) Also, users can measure the data through browser by using Ethernet auto WEB.
AC/DC 85~265V or 115~415V is both optional. Also, 380V line voltage can also serve as power supply.
Other Question? Please contact us and we will get back to you as soon as possible.